SPECIFICATIONS
SPECIFICATIONS
Specifications
The system consists of a SECELUX PRO controller along with a three-phase network analyzer that collects energy records and electrical parameters.
SECELUX PRO’s scalability and adaptability allow the integration of different hardware solutions upon request, in order to meet the technical requirements of the system.

Hardware Requirements
Power supply | 12V AC / 5A |
Number of relay outputs | 2 voltage-free contacts |
Number of digital inputs | 2 |
Connectivity | 1 x port Rs232 2 x ports Rs285 1 x Gigabit Ethernet port 1 x 100MBPS Ethernet port 2.4G/5.8G Dual Band WiFi Bluetooth 5.0 |
Communications | Built-in internal 4G modem Anti-vandal outdoor SMA antenna |
Operating system | Raspberry Pi OS 32-bit |
Mounting | DIN rail |
Space requirement | 6-9 DIN modules |
Energy measurement | Three-phase network analyzer |
Logged Parameters
Energy measurements | Total active power (W) Active energy consumption (kWh) Reactive energy consumption (kVArh) |
Electrical parameters | Voltage per phase (V) Intensity per phase (A) |
Operating parameters | Switch-on and switch-off events |
Alarms
Physical alarms | Disconnection of protections Open door |
Logical alarms | Possible line failure Panel in manual mode No input voltage |
Features
Operation control | Calendar and special days settings |
Switch-on and switch-off settings | Fixed and dynamic settings |
Energy monitoring | Logging of electrical and energy parameters |
Alarms | Sending alerts by email |
Consumption steps regulation | U6me2 protocol for remote reprogramming from the control head |